← Dashboard
🌡️
Radiator Check

Will the existing radiators work at heat-pump temperatures?

Radiators are rated at ΔT50 (mean water temp 70°C, room 20°C — the EN 442 standard). A heat pump runs far cooler, so each radiator delivers much less than its catalogue figure. This checks, room by room, whether the existing emitters still meet the heat loss at your design flow temperature — and how much bigger they'd need to be if not.

⚠️ This is an emitter sizing check, not a heat loss calculation. The room heat loss figures must come from a proper room-by-room BS EN 12831 calculation. This tool does not produce an MCS-compliant design.
1 System design conditions
Mean water temp: 42.5 °C

Most steel panel radiators use n ≈ 1.3. Column and some designer radiators can differ — check the manufacturer's data if you need exact figures.

2 Rooms & radiators
Room Heat loss
(W)
Existing rad
@ΔT50 (W)
Room
°C
ΔT Output now
(W)
Status Need @ΔT50
(W)
Upsize
0 / 0
Radiators OK
0 W
Total shortfall

Factor applied to a radiator's ΔT50 output to give its output at a given ΔT, using (ΔT ÷ 50)1.3. At a 45/40°C flow/return into a 20°C room (ΔT 22.5), a radiator delivers about 35% of its catalogue figure — so it needs roughly 2.8× the output to do the same job.

Indicative tool. Results depend on accurate room heat loss figures (BS EN 12831) and correct ΔT50 radiator data. The n = 1.3 exponent is a standard panel-radiator assumption. This check supports system design but is not a substitute for a full MCS heat pump design, and does not produce an MCS-compliant certificate.