Manufacturer firstThe manufacturer's instructions always take priority. The figures in this guide are the standard minimums (BS 5871 and BS 5440), used where the instructions say nothing or you need to check what applies.
What BS 5871 Covers
| Part | Appliance | Heat input |
|---|---|---|
| BS 5871-1 | Gas fires, convector heaters, heating stoves, and fire fronts for back boiler units (BBU) | Not stated in the scope list |
| BS 5871-2 | Inset live fuel effect (ILFE) | Up to 15 kW |
| BS 5871-3 | Decorative fuel effect (DFE) | Up to 20 kW |
| BS 5871-4 | Flueless fires | Up to 6 kW |
| BS 5871-4 | Flueless convector heaters, including single-installation greenhouse heaters | Up to 4.2 kW |
| BS 5871-4 | Flueless heating stoves | Up to 6 kW |
The regulations (GS(I&U)R) set the legal requirements for safe installation and use. They do not say how to meet them. BS 5871 is the standard that does, so it is the one to work from for gas fires, convector heaters, fire/back boiler units and decorative fuel effect fires.
Any new gas fire must carry a conformity mark (CE and/or UKCA/UKNI) under the Gas Appliances (Enforcement) and Miscellaneous Amendment Regulations 2018.
How a Fire Sits in a Chimney Recess
🔥 Open-flue fire fitted to a builders opening (side view)
- Chimney carrying the flue gases away
- Lintel supporting the brickwork above the opening
- Builders opening (recess) built to suit the appliance
- Closure plate sealing the opening, normally supplied with the fire
- Flue spigot releasing the products of combustion into the opening
- Chair brick (may have to be removed, depending on the fire)
- Radiant (firebrick behind it limits heat loss)
- Hearth
- Catchment space below the spigot, collecting debris
Schematic, not to scale. Air for combustion and circulation enters at the base of the appliance. The fire heats the room by radiation and, on a radiant convector, by warm air leaving through louvres at the top.
Appliance Types
- The radiant is brittle fire clay (refractory). Rear dimples or thorns give a bigger surface and the wedge shape improves heat transfer. When hot it glows (incandescent) at normally over 850 °C. The slotted front lets secondary air in, which improves combustion.
- A radiant convector adds a heat exchanger. It may have a ceramic radiant, imitation fuel (logs or coals) or pebbles, and can be open flue (Type B) or room sealed (Type C), natural or fan draught.
- Open-flue fires are made for a normal masonry chimney but may suit precast flue block, a fabricated flue with a collector or box, or a proprietary fan flue such as an SE vent.
- Over 7 kW an open-flue appliance needs purpose-provided ventilation (BS 5440-2). Most manufacturers keep gas fires under 7 kW to avoid it.
- A fire front for a back boiler unit (BBU) is made for that BBU. Never fit it without the BBU, and no other fire than the one the manufacturer specifies. If a fire is used with a circulator, ask the manufacturer to confirm it is suitable.
- Only where the manufacturer permits. These are specially designed for direct connection and cannot be installed by conventional methods. A conventional fire must never be fitted this way.
- Open flue (Type B1). The draught diverter is normally at the back of the fire, before the flue connection. Flue outlet is top or rear. No products pass into a builders opening, so no back plate is needed.
- Unless the manufacturer says otherwise, connect only into a lined chimney by one of: metal twin wall flue to BS EN 1856-1, metallic flexible liner to BS EN 1856-2, a lined masonry chimney (for example clay lined), or a factory-made insulated chimney to BS EN 1859.
- Joints between appliance and flue are mechanically held (clamp or self-tapping screws) and sealed (for example high temperature silicone or fire cement).
- A continuous run from the appliance to the terminal. A terminal is always fitted, whatever the flue diameter.
Liner and register plate details are on the Flues & Chimneys tab.
- Heat the surrounding air by natural or forced convection. Generally room sealed (Type C) and wall mounted. A forced convection model has a circulation fan under the appliance.
- The burner sits in a sealed heat exchanger. Cool room air enters at the bottom, is warmed by the heat exchanger and leaves through louvres at the top. Combustion air comes in through the outer tube of the concentric flue and the products of combustion leave through the inner tube. A decorative casing covers the heat exchanger.
- On a fanned model the combustion fan draws air in and pushes the products out through the concentric flue. A safety interlock must stop the appliance running if the combustion fan fails.
- The seals on the heat exchanger and flue are critical to safe operation (room sealed).
The benefits of a fan convector: it heats the room faster and the flue system can be smaller, so it is less obtrusive and easier to fit.
- Free-standing appliances that imitate a solid fuel or wood-burning stove, traditional or contemporary in style. Nominal heat input is 3.6 kW to 6.3 kW net (BS 5871).
- May be flueless (Type A), open flue (Type B) or room sealed (Type C). Install as the manufacturer directs: into a normal fireplace opening through a closure plate, by direct connection, or with an independent flue system (normally vitreous enamel).
- Simulated logs or coals imitating a live fuel fire, partly or fully recessed into a builders recess or opening. Flue is open or room sealed. Up to 15 kW (BS 5871-2).
- Depending on the manufacturer, suitable for a masonry chimney, fabricated flue, appliance-specific fan flue, proprietary fan flue, room sealed (natural or fan) or direct flue connection. Can be part of a fire/back boiler assembly if the manufacturer specifies.
- Parts: chimney; builders opening with a debris collection void at the back; chair brick (may be removed); lintel; no closure plate, so the opening is sealed on all sides to the wall or surround with foam or fibrous seal around the back box; back box secured by screws through the front lip or by tie wires to an eye bolt at the back of the catchment space, with a decorative trim in front; burner in a box (open or filled with vermiculite or perlite) with the radiant surface above it and normally no guard at the front; heat exchanger if the manufacturer fits one.
- The flue spigot is usually near the top of the appliance. That keeps debris build-up from blocking it and delivers the products to the throat of the chimney.
- An appliance that slots into a fabricated firebox built into a purpose-made builders opening, normally a raised opening (a hole in the wall).
- The flue connection is on top of the firebox. Mostly fitted to a lined chimney. If the manufacturer permits, an unlined chimney can be used with the optional flue kit.
- The flue kit stops debris reaching the firebox and is used only with the appliance it is made for. Fit it only where the chimney has passed inspection and a flue flow test, and has been swept if it was used for solid fuel.
- Do not fit a flue kit where condensation is known or suspected to be a problem. If the kit connects onto a short length of flexible liner, that liner must be to BS EN 1856-2.
- BS 5871 normally requires 50 mm between the flue outlet and any surface. With a flue kit this does not apply, because the fire sits in its own housing connected directly to the kit.
- Used for looks rather than heat. A standard basket-type fire can be as low as 20 % efficient. The radiant surface is imitation logs, coals or pebbles. Open flued (Type B), natural or fan draught, into a builders opening, fireplace recess or under an independent canopy. Heat inputs up to 20 kW net.
- Parts: chimney; builders opening or recess built to suit the appliance; chair brick (may be removed); lintel; burner in a box (open or vermiculite/perlite filled) with imitation fuel or pebbles and no guard at the front, so there is a risk of contact by people or clothing.
- The appliance is not protected against falling debris from the flue, which can cause poor combustion and damage the imitation fuel. A blocked flue shows up as flame displacement and a lot of products entering the room. Large amounts of room air are also drawn into the flue, which can cause draughts.
- Designed to work without a flue. The products of combustion go straight into the room, so there is a risk of a vitiated atmosphere and condensation in poorly ventilated rooms. Ventilation rules are specific to these appliances and are normally restricted to a maximum 4.3 kW net.
- BS 5871-4 does not cover: portable appliances to BS EN 449 (LPG cabinet heaters); closed-flue fires in motor and touring caravans; appliances in boats; installations in horticultural premises; installations in transportable accommodation units.
- May fit a purpose-made builders recess, stand on the floor or fix straight to a wall.
- Wall-mounted (hall heater): the burner sits inside a casing and is protected from direct heat by a combustion box around it. Air enters through louvres at the bottom or front and the warm air and products leave through louvres at the top.
- Catalytic type: the products pass through a catalyst that breaks down contaminants such as carbon monoxide, leaving carbon dioxide and water vapour. The unit is sealed at the front with a glass panel so all the gases go through the catalyst. Never run it without the front, or with damaged glass, because incomplete combustion products would be released. Air enters at the base.
- Makers claim 100 % efficiency because there is no flue loss. The main problem is condensation from the water vapour, so ventilation is paramount.
Where a Gas Fire Can Go
- Bathroom or shower room: an open-flued appliance must not be installed there (GS(I&U)R and BS 5871).
- Sleeping accommodation: any space heater above 12.7 kW net (14 kW gross) must be room sealed.
- Below 12.7 kW net, room sealed is still preferred. If an open-flue appliance is fitted it must have an acceptable atmosphere monitoring device that safely shuts it down if unacceptable levels of combustion products are detected. If you are unsure the device is suitable, do not install the fire.
- Private garages: space heaters may be installed unless the manufacturer says otherwise. For vehicle repair and body shops, see IGEM/UP/18.
Never in the builders openingVentilation shall follow BS 5440-2, and in all cases a vent opening must not be fitted within the builders opening. Where radon is known or suspected, the vent must not communicate with the under-floor space or disturb any radon protection measures.
Open-Flue Fires (Radiant, Radiant Convector, ILFE)
- In most dwellings the adventitious ventilation is adequate for safe operation. Think again where the house has been upgraded with double glazing, cavity insulation, draught proofing and the like, and in new-build construction. These can cut the air available.
- If there is doubt, fit purpose-provided ventilation.
- Extractors such as kitchen fans, cooker hoods (especially ducted), paddle fans and the like can create below-atmospheric pressure or turbulent air that upsets the flue. Where this is noted and could affect safe operation, extra purpose-provided ventilation must be installed.
- Where the heat input exceeds 7 kW net, add 5 cm² of effective free area for every kW above 7 kW net (BS 5440-2).
Multi-appliance: ventilation is not normally needed for two open-flue space heaters in interconnected rooms if the flue systems are of similar construction and height and the total rated heat input does not exceed 14 kW net. If any of those conditions is not met, add ventilation. Put the permanent vent between the appliances where practical. This does not apply to DFE fires, or to a fire/BBU, where the BS 5440-2 multi-appliance rule is used.
Decorative Fuel Effect (DFE)
| Situation | Ventilation |
|---|---|
| One DFE fire | 100 cm² (includes an allowance for adventitious air) |
| Two DFE fires in the same room or internal space | 235 cm² (100 + 100, plus 35 for the adventitious allowance of the second fire) |
| Two DFE fires in a through room that was originally two rooms (wall removed) | 200 cm², with no extra 35 cm² |
| DFE with other appliances in the same room, internal space or through room | Total for the DFE fire(s) plus the BS 5440-2 multi-appliance rule for the others |
| DFE fires only, open flue appliances in the same room or space | 5 cm² per kW (no adventitious allowance), not 5 cm² per kW above 7 kW. In a through room this applies only where two or more DFEs are fitted. |
- An air vent must not communicate directly with the builders opening or fireplace recess. Block off any existing under-floor air supply into the opening, because it causes draughts that upset the burner or flue.
Other appliances in the room? Add the BS 5440-2 multi-appliance figure for them to this total.
Flueless Fires and Heaters
- The room or internal space must have an openable window or other means of ventilation direct to outside.
- A ventilation route must not communicate with the builders opening or recess, or any other internal space (unless it is ducted through that space direct to outside), including below-floor areas.
- Site the appliance at least 1 m from any vent opening, so combustion air and any other ventilator in the area do not disturb the flame.
- Take care when installing under an existing chimney, in front of a fireplace opening, or near an existing flue. Air movement must not disturb the flame picture and cause incomplete combustion, overheating and sooting. Unless the manufacturer says otherwise, seal the base of any redundant chimney or flue.
- Two or more flueless appliances must not go in the same room unless the room volume is adequate for the individual need of each.
- In front of a redundant solid fuel back boiler: it is preferable to remove the boiler and seal the opening. If it stays, it must not be left so pressure can build up. Keep the open vent intact to its termination point if you can. If the vent is removed or cut, drain the unit and remove any waterway access covers, or drill a hole of at least 6 mm in the boiler.
Room means an occupied (habitable) area such as a living room, lounge, kitchen or dining room, including a conservatory. An internal space is not occupied: a hallway, cupboard or landing. For ventilation, an integral greenhouse counts as an internal space. An integral greenhouse is joined to the dwelling by a door or window. An independent greenhouse is completely detached and not connected to the dwelling by any means.
| Where | Min room volume | Ventilation |
|---|---|---|
| Room (occupied, including conservatory) | 1 m³ per 45 W of rated input | 100 cm² fixed up to 2.7 kW net, plus 55 cm² per kW above 2.7 kW |
| Internal space (hall, landing, cupboard, integral greenhouse) | 1 m³ per 90 W of rated input | 100 cm² fixed up to 5.4 kW, plus 27.5 cm² per kW above 5.4 kW |
| Independent greenhouse | Not stated | None up to 2.7 kW. Above 2.7 kW both a high and a low vent, each 39 cm² per kW above 2.7 kW. |
If the minimum room volume is not met you cannot fit the appliance: choose one with a lower heat input. Heaters are normally limited to 4.3 kW net.
Worked examples from the book: 4 kW heater in a 6 × 7 × 2.4 m room: volume 100.8 m³, minimum 88.9 m³, ventilation 171.5 cm². 3.5 kW heater in a 3 × 6 × 2.4 m hall: volume 43.2 m³, minimum 38.9 m³, ventilation 100 cm². 3.7 kW heater in an independent greenhouse: 39 cm² high and 39 cm² low.
Check the flue before you fitFor an open-flue appliance, carry out a visual inspection, a flue flow test and a spillage test (BS 5440-1). If the chimney has previously served oil or solid fuel it must be swept first. Do not leave an appliance operating if the flue's integrity is in question.
Chimney Size
| Appliance | Minimum chimney diameter |
|---|---|
| Gas fire, ILFE | 125 mm |
| DFE | 175 mm (a 225 × 225 mm brick chimney is adequate) |
For a DFE the chimney size also depends on the height of the chimney and the fireplace opening area. Use the calculator and examples further down this tab, and BS 5871-3.
Types of Flue
| Flue type | Notes |
|---|---|
| Masonry chimney, lined or unlined | Most common. Unlined needs a flue kit or manufacturer approval for the appliance. |
| Precast flue blocks | See below. Inspect carefully. |
| Prefabricated flue box and pipe | Factory-made system to BS 4543, BS 715 or BS EN 1856-1 and 2. |
| Proprietary fan flue (SE vent) | Fan-assisted through an external wall. See below. |
| Manufacturer-specific fan flue | Only with its own appliance. |
| Room sealed, natural draught or fanned | Seals are critical. See below. |
Preparing an Existing Chimney
- Dampers must be removed or fixed fully open. Wear suitable PPE when clearing soot and debris.
- Clear the catchment space below the opening and remove any air box.
- Where the old fuel was solid or oil, sweep the chimney and confirm it suits gas before fitting.
Chimney Liners
| Liner | Standard |
|---|---|
| Flexible metallic liner | BS 715 / BS EN 1856-2 |
| Clay liner | BS EN 1457 / BS 65 |
| Poured concrete liner | BBA certified |
Flexible liner rules
- A continuous, rising run, with no part more than 45° from vertical.
- Mechanically secured and sealed at the top and bottom, normally with a clamp plate.
- Mineral wool supported around the liner as specified.
- Where a register plate is used, the liner must not protrude more than 25 mm into the opening.
🧱 Direct flue connection to a lined chimney
- Fire's flue liner passes up into the chimney liner
- Clay chimney liner
- Register or clamp plate in the chimney throat
- Joint, mechanically held and sealed
- Direct flue fire
Schematic. The flue liner of a direct flue fire must run at least 150 mm up into the clay liner, with the register or clamp plate fitted in the throat. Follow the manufacturer's instructions for the exact fitting.
Precast Flue Blocks
- Made to BS EN 1806 and BS EN 1858.
- Older blocks (for example aerated) can deteriorate and have a smaller cross-section. Inspect carefully, especially the transition in the roof space.
- A flexible liner is not permitted in a precast block flue. Fit cooler plates where specified.
- If the integrity of the flue is in question, do not leave the appliance operational.
Prefabricated Flue Boxes and Fan Flues
- Prefabricated flue box and pipe (BS 4543, BS 715, BS EN 1856-1 and 2). Must not protrude into a garage or out of an external wall.
- Proprietary fan flue (SE vent): a gather box collects the products, and a fan in a weatherproof external box draws them out under negative pressure. An interlock stops the appliance if the fan fails. The back plate is cut and sealed, with an infill panel. Drawbacks are noise and the electrical supply.
- Manufacturer-specific fan flue: use only with its own appliance. The fan flow proving is supplied with it.
Room Sealed and Condensing Appliances
- Room sealed: check the seals at installation and at every maintenance visit. Take care through a cavity wall, fit the drip ring, and make sure there is an interlock on any mechanically assisted flue.
- Condensing fires condense at around 55 °C and run at roughly 65 to 75 % up to over 90 % efficiency. They use a small-bore GRP flue and need a condensate drain. Check the flue and chimney are suitable for condensing appliances.
Terminals and Hearth Plate
- A flue of 170 mm or less needs an approved terminal. Flues over 170 mm generally do not require one, depending on conditions. A direct flue fire always needs a terminal.
- Bird guard opening not more than 20 mm, made of corrosion-resistant material.
- Hearth plate (Building Regulations): when the flue specification is changed, fix a durable plate near the meters, water isolation valve, or the chimney or hearth. It must show: location, chimney designation, category (for example Class 1), appliance types including whether suitable for condensing, type and size of flue, installation date, and any other relevant information.
DFE Flue Size: Fireplace Opening Area
For a wall-mounted or suspended canopy, the chimney size for a DFE depends on the fireplace opening area and the chimney height (BS 5871-3, Fig 18.26). First check the canopy meets all the constraints.
- Canopy front taper not more than 45°.
- Canopy height above the fire bed not more than 400 mm.
- Fire bed sides at least 300 mm from the canopy edge.
- Side elevation angle not more than 45°.
- Fire bed front at least 100 mm from the front of the canopy.
Suspended canopy: height not more than 400 mm, front taper not more than 45°, bed sides at least 300 mm from the canopy edges on all sides, side angle not more than 45°.
📐 Wall-mounted DFE canopy constraints (side view)
Schematic, not to scale. All constraints must be met together. Where they are not, use the larger area formula in the calculator below.
Book examples: a canopy 0.9 × 0.3 m with all constraints met gives 0.27 m², and a 6 m chimney then needs a 175 mm flue. With constraints not met (H 0.3, W 0.9, D 0.3): 0.3 × (0.9 + 0.6) = 0.45 m², and 6 m gives 250 mm. BS 5871-3 example: 0.9 × 0.75 = 0.68 m², 6 m gives 300 mm. This guide does not reproduce the Fig 18.26 chart: read the flue size from the standard.
Formulas: constraints met, rectangular W1 × W2, circular π × W1² ÷ 4. Not met, wall-mounted H × (W + 2D), suspended 2 × H × (W1 + W2), circular π × W1 × H.
Builders openingThe opening or recess the fire sits in. Its size, the debris catchment space below the flue spigot, and the way it is sealed all affect safe operation. The manufacturer's instructions override the general figures here.
Maximum Void Size
📦 Largest void for radiant, radiant convector, stove and ILFE
Maximum void (Fig 18.27). If the opening is bigger, reduce it with infill panels, a sealed fire surround, or by bricking up. No combustible material may be left in the opening.
Spigot and Catchment Space
📏 Open-flue fire into a chimney throat (side view)
Schematic, not to scale. The spigot is also at least 50 mm (sideways) from any obstruction.
- Outset (floor-standing) fire: the spigot must be at least 50 mm sideways from any obstruction and 250 mm above the base of the catchment space, and it must protrude at least 15 mm into the opening.
- Wall-mounted fire: the 250 mm is measured from the level of the inner wall brick.
- Flue throat (gap at the top of the opening): 110 mm ± 10 mm.
- Inset fires only need a 50 mm arc round the spigot plus an adequate void, as the manufacturer states.
Debris Catchment Volume
| Chimney | Minimum catchment space |
|---|---|
| Lined masonry, new or previously used for gas Block flue, new or previously used for gas | 2 dm³ at a depth of 75 mm |
| Unlined masonry Lined, previously solid fuel or oil Block, previously solid fuel or oil | 12 dm³ at a depth of 250 mm |
1 dm³ = 1,000,000 mm³ (one litre). Check the figures against Table 18.1 of the NICEIC Guide for your installation, and against the manufacturer's instructions.
DFE Flue Kit and Catchment
- Minimum catchment 12 dm³, measured from below the lowest point of the debris collector slots.
- Use spacer bars as the manufacturer supplies, and dense concrete for any infill. Do not use lightweight aerated block.
- The catchment space must be accessible for inspection and cleaning.
- The chimney must be at least 50 mm larger than the maximum cross-section of the debris deflector.
- Fit the warning label where the fire is installed in an unlined chimney.
Closure Plate
- The plate must be sealed on all sides. Do the flue flow test before fitting a closure plate in front of the fireplace.
- Sealing tape must withstand over 100 °C. Use PRS10 tape on smooth surfaces. On uneven surfaces use a non-setting, fire-resistant mastic plus mechanical fixing.
- Do not tape over air relief openings unless the manufacturer says so. No nylon or plastic wall plugs.
- Renew the seal at every service.
Sealing the Builders Opening
- Seal round the fire surround, pipe and cable holes, where a flexible liner enters the chimney, and any other unspecified opening such as an under-floor air supply or the surround of an ILFE.
- Unwanted air entering the opening upsets the flue and the flame picture.
Spigot Restrictor and Extension
- Restrictor: fit only where the manufacturer specifies. Never fit one to a precast block flue unless the manufacturer specifies it.
- Extension: use the manufacturer's own only. The extension must protrude at least 15 mm into the back plate opening and the outlet must be 50 mm from any obstruction. Infill panels must be fire resistant.
- The book's text gives a 150 mm maximum for an extension, but its figure labels 150 mm as "min or as per manufacturer's instructions". The manufacturer's instructions govern.
Types of Fireplace for a DFE
| Type | Description |
|---|---|
| Builders opening / recess | A purpose-built opening in the chimney breast |
| Raised opening | A hole in the wall, raised above floor level |
| Opening with independent canopy | Builders opening topped by a separate canopy |
| Wall-mounted independent canopy | Canopy fixed to the wall over the fire bed |
For canopy sizing and the chimney size, see the Flues & Chimneys tab.
Burn riskNaked flame and incandescent surfaces ignite nearby combustible materials and burn people. Hearths, floor heights, side clearances and guards all control that risk. The manufacturer's instructions take priority over the figures here.
Hearth: Wall-Mounted Fire
- A wall-mounted BS 5871-1 fire needs a hearth unless it conforms to BS 7977-1.
- Flame or incandescent surface at least 225 mm above a combustible floor covering, or at least 300 mm above the finished floor where there is no covering. The 300 mm allows for a carpet being laid later.
- Hearth must be non-combustible (BS 476-4 or Class O), at least 12 mm thick, projecting at least 300 mm forward from the back plane of the fire and at least 150 mm beyond any naked flame or incandescent material.
- The height at which a shelf can be fitted above the appliance is specified by the manufacturer.
📐 Hearth for a wall-mounted fire (plan view)
Schematic, not to scale. The 300 mm is measured forward from the back plane of the fire. The 150 mm is measured from the edge of the naked flame or incandescent material.
📏 Height of the flame above the floor (side view)
Schematic. Where there is no floor covering, use 300 mm so a carpet fitted later will not bring the flame too close to it.
Hearth: ILFE and DFE
- The hearth extends into the builders opening, at least 12 mm thick (thicker if the surface below the hearth would exceed 80 °C).
- It projects at least 300 mm forward of the naked flame or incandescent material and at least 150 mm to each side.
- Where a non-combustible side wall is within 150 mm of the flame, the hearth extends up to that wall.
- A fender or up-stand at least 50 mm high runs along the front and sides of the hearth.
- Hole-in-the-wall (raised opening): the manufacturer may specify that no hearth is needed. The flame or incandescent surface is still at least 225 mm (300 mm with no floor covering) above the floor. Where a hearth is fitted, the height from the floor (Y) plus the hearth depth (X) is shown in the book's figure as at least 225 mm. Follow the manufacturer.
Side Walls and Combustible Materials
| Item | Minimum distance |
|---|---|
| Combustible side wall to flame / incandescent surface | 500 mm |
| Convector: to warm air outlet | 150 mm, or as the manufacturer states |
| Canopy or flue pipe, up to 1 m above flame / fire bed, to combustibles | 300 mm |
| Canopy or flue pipe, over 1 m above flame / fire bed, to combustibles | 50 mm (BS 5440-1, single-skin pipe) |
Insulated or double-skin pipe is preferred.
Protecting the Customer
- A radiant fire needs a dress guard (BS 1945) or a fireguard (BS 8423), permanently fixed. A glass front counts as a guard (BS 7977-1, PD 6516).
- Under BS 5871 clause 20, leave instructions with the customer, particularly for the young, elderly or infirm.
- ILFE and DFE do not normally have a guard.
- Floor-level fire (no guard): fit a compliant hearth plus a barrier (fender, kerb or horizontal bar) at least 50 mm and not more than 1000 mm from the floor, at least 300 mm in front of the naked flame or incandescent refractory and 150 mm beyond its edge.
Gas Supply to the Fire
- Pipework to BS 6891 or IGEM/UP/2, in malleable iron, mild steel, copper or stainless steel.
- No flexible pipework to a flued domestic appliance (the Guide cites Reg 26(2)), except a gas tumble dryer.
- Not in a cavity wall (the Guide cites Reg 19(4)), unless it supplies a live fuel effect fire fitted in the cavity. Then the run must be short, in a gas-tight sleeve, sealed where it enters the fire.
- Fit an isolation valve and a means of disconnection downstream of it, unless it is not reasonably practicable.
- Concealed pipe must be protected against corrosion (coated soft copper or PVC tape). Soot and cement attack metal.
- Through a solid floor or wall: use a gas-tight sleeve, sealed at one end with a fire-resistant, non-setting mastic.
Surface Connection to a Fire
- Use the manufacturer's appliance elbow and floor plate. The size of the hole in the floor matters.
- Extension piece and dress rings: dress rings do not seal the opening.
- Drop lever valve: keep it greased. It can seize.
- Pedestal elbow: the sealing cap must be gas tight. Do not seal the threads.
Controls: The Seven Categories
- Flow controls: appliance isolation valve (AIV) or gas cock, gas tap, solenoid valve.
- Stiff tap: isolate at the AIV or the emergency control valve (ECV). Never use the screw-down valve on the pedestal elbow to isolate.
- Solenoid valve: not serviceable. Test that it closes, using a mini tightness test or let-by test.
Safety Devices
- Two-port burner. As the room atmosphere becomes vitiated, the pilot flame lifts away from the thermocouple, which shuts the appliance down.
- Full shutdown at about 1.5 to 2 % CO₂ or 200 ppm CO. Not serviceable and there is no industry test for it.
- A disc or liquid-expansion thermostat fitted near the draught diverter. It interrupts the thermoelectric current if hot products spill.
- If it has been bridged out, treat it as an immediately dangerous (ID) situation under the Gas Industry Unsafe Situations Procedure (IGEM/G/11), and possibly reportable under RIDDOR.
- A differential pressure switch or paddle switch. Motor current monitoring is also an approved method.
Ignition
| Type | Notes |
|---|---|
| Taper / match | Manual lighting |
| Permanent pilot | Pilot burns all the time |
| Filament glow coil / hot surface | Heated element lights the gas |
| Spark: piezo, capacitor discharge, electronic pulse | Spark at the burner or pilot |
| Direct spark ignition (DSI) | Spark lights the main burner directly |
| Intermittent pilot | Pilot lit only when there is a call for heat |
Faults are specific to the ignition type. Check the manufacturer's fault-finding guide.
Flame Monitoring and Thermostats
- Flame monitoring is by thermoelectric (thermocouple) or flame rectification.
- Thermostats are mechanical or electrical: liquid expansion, bimetallic disc or thermistors.
Commissioning
If it is unsafeIf you find the installation unsafe, disconnect it and label it as unsafe. The Guide cites Reg 33(1) for six checks: flue effectiveness, combustion air, operating pressure, gas tightness, installed in line with the regulations and manufacturer's instructions, and safe operation of the safety controls.
- Site suitability: location, ventilation, flue, hearth, clearances and floor height as covered on the other tabs.
- Flue flow test before fitting a closure plate in front of a fireplace.
- Tightness test, then purge.
- Check the electrics (where fitted), and test all the controls.
- Check the burner pressure or heat input, and the flame picture.
- Flueless appliances: combustion analysis to BS 7967 at commissioning and at every maintenance.
- Spillage test (open flue). Use a smoke match placed where the manufacturer states. Radiated heat from the fire can burn the person holding it.
- Advise on a CO alarm. It is a legal requirement for fixed combustion appliances (excluding cookers) in the rented sector in England and Wales, and in all homes in Scotland and Northern Ireland.
- Hand over the instructions to the customer (the Guide cites Reg 29), and fit the hearth plate if the flue specification changed.
Example from the book: a Valor Contour fire marks a smoke match position of 15 mm (Fig 18.62). Always use the position in the instructions for the fire in front of you.
Maintenance
- You must follow GS(I&U)R duties on every visit.
- The appliance data plate must be readable.
- Follow the manufacturer's service procedure. The NICEIC Guide gives a 27-step service procedure and an 18-step dismantle-and-clean procedure.
- Renew the closure plate seal at every service.