IGEM/UP/1B Edition 4 (March 2026) changed tightness testing so that permissible pressure drop limits are based on the Installation Volume (IV) of the system — not the meter badged capacity.
Edition 3 runs alongside Edition 4 until 30 September 2026, then is withdrawn. Edition 4 becomes mandatory on 1 October 2026.
How IV is calculated
A = Sum of pipe internal volumes
B = A × 1.1 (pipe + 10% fittings)
C = Meter internal volume
IV (D) = B + C
Purge Volume = IV × 1.5
Two modes
Pre-test reference — calculate IV, permissible drop and purge volume before you test, so you know what drop you can accept
Test result — enter the pressure drop you observed during your 2-minute test and get a PASS/FAIL verdict against the Edition 4 permissible limits
Perceptible movement
Per IGEM/UP/1B Edition 4:
Fluid (water) gauge: ≤ 0.25 mbar = not perceptible
Under Edition 4, after a pass with appliances connected, you must isolate all appliances and repeat the test. There must be no perceptible movement on the pipework-only retest. If isolation isn't practicable, the no-perceptible-movement criterion applies on the original test.
Important — Guide only
This calculator is provided as a guide only and supports the estimation of installation and purge volumes in accordance with IGEM/UP/1B Edition 4. It does not replace formal training, current standards or manufacturer instructions.
The user is responsible for verifying all values and ensuring work is carried out in line with current regulations and safe working practices.
⚠️
IGEM/UP/1B Edition 4 (March 2026)
Permissible drops are now based on Installation Volume (IV), not meter size. Edition 3 runs alongside until 30 Sept 2026, then withdrawn. Mandatory from 1 Oct 2026.
⚠️ Guide only. This calculator supports the estimation of installation and purge volumes in accordance with IGEM/UP/1B Edition 4. It does not replace formal training, current standards or manufacturer instructions. The user is responsible for verifying all values and ensuring work is carried out in line with current regulations and safe working practices.
🎯 Step 1 — What do you want to do?
Choose Pre-test Reference if you haven't tested yet and want to know what pressure drop is permissible. Choose Test Result if you've completed your 2-minute test and want a pass/fail verdict.
⛽ Step 2 — Fuel Type
Select the fuel gas in the installation you are testing.
📏 Step 3 — Pipework Lengths
Enter the total length in metres for each pipe size used. Leave unused fields blank or as 0.
Copper
Steel / Stainless Steel
⚙️ Step 4 — Meter Type
The meter's internal volume forms part of the total IV under Edition 4.
A — Pipe volume0.00000 m³
B — Pipe + 10% fittings (A × 1.1)0.00000 m³
C — Meter volume0.00000 m³
D — Total IV (B + C)0.00000 m³
📉 Step 5 — Pressure Drop Observed
Enter the pressure drop you observed during the 2-minute tightness test, or tick "no perceptible movement" if there was none.
Perceptible movement thresholds (Edition 4):
• Fluid (water) gauge: ≤ 0.25 mbar = not perceptible
• Electronic gauge: ≤ 0.25 mbar = not perceptible
• Electronic gauge (1 decimal place): ≤ 0.2 mbar = not perceptible