Radiator Sizing

Room heat loss · Radiator output at your flow temperature

← Dashboard
1 · The room
City figures: CIBSE Guide A 99.6% values, as used by the MCS heat load calculator.
2 · Outside walls, windows & doors
Width × height of each window, added up.
Counted as 1.7 m² each, U 3.0.
3 · Above & below
4 · System temperatures
Optional extra on top of the calculated heat loss.
Result
Room heat loss
—
— BTU/h
Radiator to buy (catalogue ΔT50)
—
— BTU/h

Enter the room size to calculate.

Breakdown
How it's calculated & sources

Heat loss = fabric loss + ventilation loss.

  • Fabric: U-value × area × (room temp − outside temp) for each outside wall, window, door and loft ceiling. Solid ground floors use a ground temperature of 10 °C (MCS guidance). Suspended timber floors use the outside temperature because the void is ventilated (errs on the safe side).
  • Ventilation: 0.33 × air changes per hour × room volume × (room temp − outside temp).
  • Radiator output: catalogues quote output at ΔT50 (75/65 °C water, 20 °C room). At other temperatures output = catalogue × (ΔT ÷ 50)1.3, where ΔT = mean water temperature − room temperature. The exponent varies slightly by radiator; 1.3 is the typical figure for panel radiators.

Figures used

  • Room temperatures: CIBSE Domestic Heating Design Guide (2026) Table 2-2, as used in the MCS heat load calculator. Before 2007: living, dining, study and bedrooms with en-suite 21 °C; bathrooms 22 °C; bedrooms, kitchens, halls, landings and utilities 18 °C. 2007 or later: 21 °C everywhere, bathrooms 22 °C.
  • Outside temperatures: CIBSE Guide A (2015) Table 2.5, 99.6% values (via MCS).
  • U-values: RdSAP 2012 default tables (walls S6, lofts S9, windows S14). Floor and door U-values are typical estimates. Change the selections if you know the actual construction.
  • Air changes: "Older, draughty" uses the CIBSE Domestic Heating Design Guide Table 3.8 rates for pre-2000 homes (living 1.5, bedroom 1.0, kitchen and hall 2.0, bathroom 3.0). These are known to overestimate, and the current EN 12831 method roughly halves them, so "Average" uses half. "Modern / airtight" uses 0.5 per hour.

This is a quick room sizing tool. Heat flow between heated rooms at different temperatures isn't counted. For heat pump design and MCS work, a full room-by-room heat loss to BS EN 12831 is required.