Smart Meter Gas Rating

Electronic & smart gas meters

Landis+Gyr Libra

Meter Index00035.810 m³ABA (red button)

Schematic only, not to scale. The numbers on the display are an example. Your meter may look slightly different. The highlighted part is what you press.

How to recognise it

Libra series modular meter with a red button and a dark button below the display, marked A and B. Some models have a prepayment card slot below the buttons.

Steps

  1. Run the appliance with its controls set to stay on.
  2. Press the red A button and start the stopwatch at the same moment. The display shows “Please wait…” after a short delay. The meter records the index on this first press and shows it afterwards.
  3. The display then shows either the Meter Index or “Credit ON”. If it shows “Credit ON”, press A again, once or more, until the Meter Index screen appears. Note the reading. The display goes blank after a short while. Remember how many presses it took.
  4. After exactly 2 minutes press A to wake the display. If you needed extra presses the first time, repeat the same number to reach the Meter Index. Note the final reading. The final reading is the one recorded at the first press of A to wake the display.
  5. Turn the appliance off and work out the gas rate in the Gas Rating Calculator (Metric tab, 2 minutes).
  6. Reset the appliance controls to the customer’s requirements. On a boiler with a commissioning mode that overrides modulation, return it to normal operation.

Repeat if it looks over-ratedOn rare occasions the meter module is slow to talk to the base meter, and the result can suggest the appliance is over-rated by up to 4%. If that is what you see, repeat the gas rating.

Secure Meters (UK) Liberty EG4v 10

VOLUME TSTON MAN123456789A0BKey #9 (highlighted)on the keypad

Schematic only, not to scale. The numbers on the display are an example. Your meter may look slightly different. The highlighted part is what you press.

How to recognise it

Liberty EG4v 10 with a number keypad (0 to 9) beside the display, plus coloured A and B keys. The display shows ON or MAN. Secure Meters was formerly PRI.

Steps

  1. Run the appliance with its controls set to stay on.
  2. Start the stopwatch and press #9 on the keypad at the same time. The display wakes (backlight on for about 5 seconds). Press #9 twice more straight away, three presses in total, to bring up “VOLUME TST”. “VOLUME TST” shows for 2 seconds, then the meter index to 4 decimal places for a further 2 seconds. Note the starting index. The display then cycles through nine more screens and goes blank after about 35 seconds. The index is recorded at the first press and shown after the extra two presses.
  3. After exactly 2 minutes press #9 three times to wake the display and cycle to the meter index. Note the final reading. The final reading is the one recorded at the first press of #9.
  4. Turn the appliance off and work out the gas rate in the Gas Rating Calculator (Metric tab, 2 minutes).
  5. Reset the appliance controls to the customer’s requirements. On a boiler with a commissioning mode that overrides modulation, return it to normal operation.

Credit and tamper messages

  • “Low Credit” shows the credit left. The display may also offer A (accept) and B (ignore). Press A to accept emergency credit, or use the e-credit button on the energy monitor. When it is active, the letter P in the monitor corner changes to E (there can be a delay).
  • If the display says OFF instead of ON, the meter has run out of credit or the anti-tamper device has triggered. For low credit the customer tops up and follows the on-screen A or B prompts.
  • If the anti-tamper device has triggered, the gas supplier must be told so their representative can attend and reset the meter.

Elster BK-G4E

Current meter reading00000.471 m³Rate: 01Any of the three buttons

Schematic only, not to scale. The numbers on the display are an example. Your meter may look slightly different. The highlighted part is what you press.

How to recognise it

Model label “BK-G4 E” with the Elster name. Three navigation buttons sit below the display, which shows “Current meter reading” in m³ and a “Rate” line.

Steps

  1. Run the appliance with its controls set to stay on.
  2. Press any navigation button below the display. It wakes and shows the index in real time. Within 30 seconds, note the starting index and start the stopwatch. The display goes blank after 30 seconds.
  3. Within 30 seconds of the 2 minutes (120 seconds) being up, press any navigation button to wake the display again. When the stopwatch reaches 2 minutes, record the index.
  4. Turn the appliance off and work out the gas rate in the Gas Rating Calculator (Metric tab, 2 minutes).
  5. Reset the appliance controls to the customer’s requirements. On a boiler with a commissioning mode that overrides modulation, return it to normal operation.

Flonidan G4SZV

O00000.0240 m³Valve icon top left: must show O (open)Any navigation button

Schematic only, not to scale. The numbers on the display are an example. Your meter may look slightly different. The highlighted part is what you press.

How to recognise it

Flonidan G4SZV electronic module with navigation buttons below the display. The display has an icon in the top left corner that shows the position of the meter’s internal valve.

Valve iconMeaning
OValve open
BValve busy (opening or closing)
SValve shut

Steps

  1. Run the appliance with its controls set to stay on. Before you start, check the valve icon shows the valve open.
  2. Press any navigation button below the display to wake it. The meter index updates in 10-second cycles. Note the starting index and start the stopwatch. Let the display go back to sleep (it does this after about 30 seconds).
  3. After 2 minutes (120 seconds) press any navigation button to wake the display again. Note the final reading.
  4. Turn the appliance off and work out the gas rate in the Gas Rating Calculator (Metric tab, 2 minutes).
  5. Reset the appliance controls to the customer’s requirements. On a boiler with a commissioning mode that overrides modulation, return it to normal operation.

Itron RF1 sV

A000052.301 m³Either arrow buttonA0 = credit meter, J2 = prepayment

Schematic only, not to scale. The numbers on the display are an example. Your meter may look slightly different. The highlighted part is what you press.

How to recognise it

Itron G4 RF1 sV ZB with an orange up-arrow button and a blue down-arrow button to the right of the display. Icons on the face show Low Credit, Emergency Credit, Low Battery, Gas On, Message and Gas Off.

CodeShows
J0Credit
J1Emergency credit
J2 / A0Gas volume (the m³ index)
J3Energy
H0Message

On the label, a long press gives the letters A to K and a short press gives 0 to F.

Steps

  1. Run the appliance with its controls set to stay on.
  2. Press either arrow button (orange or blue) to wake the display. It shows the index and the letters A0 on the left of the display. Credit meter that doesn’t show A0 first: press the orange button until A0 appears. Prepayment meter: it wakes on J0. Press the blue button twice to scroll to J2, which shows the meter index.
  3. Within 30 seconds of waking the display, and at the next increment of the index, note the starting index and start the stopwatch. The display goes blank after 30 seconds.
  4. Within 30 seconds of the 2 minutes (120 seconds) being up, press either arrow button to wake the display again. When the stopwatch reaches 2 minutes, record the index.
  5. Turn the appliance off and work out the gas rate in the Gas Rating Calculator (Metric tab, 2 minutes).
  6. Reset the appliance controls to the customer’s requirements. On a boiler with a commissioning mode that overrides modulation, return it to normal operation.

Prepayment credit and valveThere must be enough credit or emergency credit before you start. If credit runs out, the meter’s internal isolation valve closes. Once credit is available the valve opens, and the meter carries out a leakage test as part of opening. Let that finish before you do the gas rate check. An open valve shows as a valve symbol with a right-facing arrow underneath. A cross through the valve symbol means it is closed.

EDMI Helios G6000

Total Volume00000.725 m³COKOK: press and hold 3 seconds

Schematic only, not to scale. The numbers on the display are an example. Your meter may look slightly different. The highlighted part is what you press.

How to recognise it

EDMI “Helios G6000” with a red C button on the left, and an OK button below the display between two arrow buttons.

Steps

  1. Run the appliance with its controls set to stay on.
  2. Press and hold OK for 3 seconds. The display wakes and shows the index.
  3. Within 30 seconds of waking the display, note the starting index and start the stopwatch. The display goes blank after 30 seconds.
  4. Within 30 seconds of the 2 minutes (120 seconds) being up, press and hold OK for 3 seconds to wake the display again. When the stopwatch reaches 2 minutes, record the index.
  5. Turn the appliance off and work out the gas rate in the Gas Rating Calculator (Metric tab, 2 minutes).
  6. Reset the appliance controls to the customer’s requirements. On a boiler with a commissioning mode that overrides modulation, return it to normal operation.

EDMI GS-60A and GS-60B

Total Volume00000.025 m³COKOK: press and hold 3 seconds
Total Volume000000.025 m³LeftRightRight grey button = OKPress and hold 3 seconds

Schematic only, not to scale. The numbers on the display are an example. Your meter may look slightly different. The highlighted part is what you press. Top: GS-60A. Bottom: GS-60B.

How to recognise it

GS-60A: OK button below the display, with arrow buttons either side.

GS-60B: no OK button. Two grey buttons sit to the right of the display, and the right one works as OK.

Steps

  1. Run the appliance with its controls set to stay on.
  2. Press and hold for 3 seconds the OK button (GS-60A) or the right grey button (GS-60B). The display wakes and shows the index. On a GS-60B, if the m³ screen does not appear first, use the navigation buttons to scroll to it.
  3. Within 30 seconds of waking the display, note the starting index and start the stopwatch. The display goes blank after 30 seconds.
  4. Within 30 seconds of the 2 minutes (120 seconds) being up, press and hold the OK / right grey button for 3 seconds to wake the display again. When the stopwatch reaches 2 minutes, record the index.
  5. Turn the appliance off and work out the gas rate in the Gas Rating Calculator (Metric tab, 2 minutes).
  6. Reset the appliance controls to the customer’s requirements. On a boiler with a commissioning mode that overrides modulation, return it to normal operation.

GS-60B grey buttons

ButtonShort press (under 1 second)Held over 1 second
Left greyScrolls the menu left and upReturns the display
Right greyScrolls right and downActs as OK
Open Gas Rating Calculator

Procedures follow Gas Safe Register Technical Bulletin 112. Open TB112 (PDF). If a meter does not behave as described, follow the current bulletin and the manufacturer’s instructions.