Multimeter Setup
Set meter to AC Volts — 600V range (or auto-range). Black probe to T1 (neutral) at wiring centre.
Red probe to the terminal being tested. System must be calling for heat with programmer and stats set correctly.
🔌 Wiring Centre — Voltage Tests (S-Plan)
| Terminal | Black probe | Condition | Expected | If wrong |
| T1 (N) |
Earth / T5 |
Always |
~0–5V AC |
High V = N/E reversal. Isolate immediately. |
| T2 (L) |
T1 (N) |
Spur ON |
~230V AC |
0V = spur tripped / blown fuse / no supply |
| T3 (CH PROG) |
T1 (N) |
Programmer CH ON, timed period active |
~230V AC |
0V = programmer CH not outputting / not timed on |
| T4 (CH OUT) |
T1 (N) |
CH demand + room stat calling |
~230V AC |
0V = room stat open / wiring break T3→stat→T4 |
| T5 (E) |
T1 (N) |
Always |
~0–5V AC |
High V = earth fault. Stop work. Isolate. |
| T6 (HW PROG) |
T1 (N) |
Programmer HW ON, timed period active |
~230V AC |
0V = programmer HW output fault / not timed on |
| T7 (HW OUT) |
T1 (N) |
HW demand + cyl stat calling (cold) |
~230V AC |
0V = cyl stat satisfied (normal when hot) or stat wiring open |
| T8 (PUMP) |
T1 (N) |
Either zone valve fully open |
~230V AC |
0V = no valve fully open / both end-switches open |
| T9 (BOILER SW-L) |
T1 (N) |
Either zone valve fully open |
~230V AC |
0V = no valve end-switch closed — boiler will not fire |
🌡️ Checking Heating is Working — S-Plan
- Set programmer CH ON. Set room stat above room temperature. Probe T3 = ~230V confirms programmer CH output is live.
- Probe T4 = ~230V confirms room stat contacts closed and CH signal reaching CH zone valve orange wire.
- CH valve motor energises on orange wire, drives valve open (allow 2–3 minutes). Listen for relay click when fully open.
- Probe T8 = ~230V confirms CH valve white end-switch has closed — pump now running.
- Probe T9 = ~230V confirms boiler switched live active — boiler should fire. Check flow/return getting hot.
🚿 Checking Hot Water is Working — S-Plan
- Set programmer HW ON. Probe T6 = ~230V confirms programmer HW output is live.
- Probe T7 = ~230V confirms cyl stat is calling (cylinder cold, C→Call1 contacts closed). If 0V and cylinder is cold — cyl stat fault or wiring break.
- HW zone valve orange wire energised. Valve drives open (2–3 minutes). End-switch closes when fully open.
- Probe T8 = ~230V (pump runs). Probe T9 = ~230V (boiler fires). Both valve whites connect in parallel — either valve alone can fire boiler and pump.
- Cylinder heats. When cyl stat satisfied (~60°C), T7 drops to 0V — HW valve de-energises, spring closes, end-switch opens — boiler and pump off.
⚠️ S-Plan Common Faults
| Fault | Likely Cause | Test / Fix |
| 🔥 |
No heating, no HW |
Spur tripped. Programmer off. Both valve oranges dead. |
Check T2 = 230V. Check programmer on. Check T4 and T7. |
| 🌡️ |
No CH, HW OK |
Room stat open. T3/T4 break. CH valve orange dead. |
Probe T3 then T4. Bridge room stat temporarily. Check orange at CH valve. |
| 🚿 |
No HW, CH OK |
Cyl stat satisfied/faulty. T6/T7 break. HW valve orange dead. |
Probe T6 then T7. Check cyl stat set 60°C. Bridge C→Call1 to test stat. |
| ⚡ |
T8/T9 = 0V — pump & boiler not firing |
Both valve end-switches open. White wires broken. Valve not fully open. |
Probe T8 at each valve white individually. Replace valve head if motor fails to open. |
| 💧 |
Pump runs, boiler won't fire |
T9 not wired. Boiler CH terminal break. Boiler lockout. |
Probe T9 = 230V. Check boiler CH/timer terminals. Check boiler fault codes. |
| 🔄 |
CH on all the time |
Room stat contacts welded. T4 permanently live. Valve orange never off. |
Disconnect room stat — if CH stops, stat is welded. Replace stat. |
| 🌊 |
Valve won't close (spring return failed) |
Spring return mechanism failed. Orange wire permanently live. |
De-energise orange wire. If valve stays open — replace valve head or full valve. |
| 🔊 |
Valve hums but won't open |
Valve head seized. Scale on spindle. Motor capacitor failed. |
Try manual lever. If seized — replace valve head. Check orange = 230V at valve. |
📋 Pro Tip — Voltage Drop Method
To confirm a wire is carrying current (not just showing voltage): probe each end of the wire. A good conductor shows the same voltage at both ends. A voltage drop of more than 5V across a wire indicates high resistance — check terminals, connections, and wire condition.
📡 Continuity Testing (Power OFF)
With system fully isolated, use Ω/continuity mode to check: room stat pin2→pin3 (closes when cold), cyl stat C→Call1 (closes when cold), valve winding continuity (typical 30–80Ω). An open circuit reading on a stat or valve coil means replace the component.